Confined Space List

This list is used primarily by Facilities Services Maintenance & Alterations and Campus Engineering & Operations. Do not start work in an area until the status has been determined. Any employee who enters a Confined Space during a work assignment must have necessary training and permits.

Under the Permit Required column these areas are designated by:

  • No identifies area as a Confined Space (CS).
  • Yes identifies area as a Permit Required Confined Space (PRCS).
  • A blank entry indicates the area is neither a CS or PRCS.

If a suspected CS or PRCS area is NOT listed on this report, please fill out a Confined Space Evaluation Form and submit it to BOX 354285.

NOTE: If your browser adds an extension other than .csv, please change it to .csv
NOTE: Formatting Tip — In Excel, turn on Word Wrap for the Hazards and Comments columns.


 
FACNUMBuildingsort iconLocationLocation DescriptionLocation DetailPicturesHazardsCommentsPermit Required
1131AEROSPACE AND ENGINEERING RESEARCH BUILDINGTIPEXPTNKTIP EXPANSION TANKBASEMENT LOW PRESSURE INSIDE,OPENING IT WILL VENTILATE (VACUUM).
ELECTRIC SENSING UNIT LESS THAN 50V.
NO
ALLALLATTIC (CLIMB OR CRAWL TO ACCESS) ATTICS YOU CLIMB/CRAWL IN ARE CS.
WORK ACTIVITIES CONDUCTED IN A CS COULD CHANGE IT TO PRCS.
NO
ALLALLATTIC (WALK IN TO ACCESS) IF YOU WALK IN AND REMAIN STANDING
THEN THE ATTIC IS NOT A CS OR PRCS.
ALLALLCEILING PLENUM CEILINGPLENUMS ARE CS EXCEPT AREAS YOU CAN WALK IN
AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS.
WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS.
NO
ALLALLCOOLING TOWER Hazard: ENTRAPMENT
Hazard: MECHANICAL
Hazard: ELECTRICAL
Hazard: CHEMICAL
YES
ALLALLCRAWLSPACE CRAWLSPACES ARE CS EXCEPT AREAS YOU CAN WALK IN
AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS.
WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS.
NO
ALLALLELECTRICAL VAULT Hazard: OXYGEN DEFICIENCY
Hazard: VEHICULAR TRAFFIC AT ENTRY POINT
YES
ALLALLHVAC PLENUMS W/ACCESS HATCH PLENUMS ARE CS EXCEPT AREAS YOU CAN WALK IN
AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS.
WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO PRCS.
NO
ALLALLHVAC PLENUMS W/ACCESS HATCH Hazard: ENTRAPMENT (SMALL SPACE)
Hazard: MECHANICAL (FAN)
Hazard: ELECTRICAL (FAN MOTOR)
YES
ALLALLHVAC PLENUMS W/DOORS IF YOU CAN WALK INTO THE PLENUM
AND STAND IN THE WORK AREA, IT IS NOT A CS.
ALLALLPIPE CHASES ACCESSED BY HATCH PIPECHASES ARE CS EXCEPT AREAS YOU CAN WALK IN
AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS.
WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS.
NO
ALLALLSANITARY SEWER MANHOLES Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
ALLALLSTORM DRAIN MANHOLES Hazard: ATMOSPHERE (TOXIC)
Hazard: ENGULFMENT (WATER)
YES
1351ANDERSON HALLUTILTUNNELUTILITY TUNNELMECHANICAL ROOM OR VIA HATCH IN RM 22 Hazard: ATMOSPHERE (SEWER GAS FROM FLOOR DRAINS)
YES
1180ARCHITECTURE HALLATTICAUDATTIC OVER AUDITORIUMACCESS BY ROOF Hazard: FALL (AREAS WHERE FLOOR IS CEILING FOR ROOM BELOW)
IF CRAWLING, AREAS W/BOARDS ARE CS,
AREAS WHERE FALL HAZARD EXISTS ARE PRCS.
NEED WR TO COVERHOLES W/PLY.310B 1/2 DOOR NEEDS HINGEREPAIR.
YES
1180ARCHITECTURE HALLATTICSPACEATTIC SPACEHATCH OFF STAIRWAY (OVER STUDENT CAFÉ) Hazard: FALL (FLOOR IS SUSPENDED CEILING FOR ROOM BELOW)
ACCESS IS BY CRAWLING.
YES
1180ARCHITECTURE HALLPIPECHASEPIPE CHASE UNDER FLOOROUTSIDE ROOMS 13, 32, & 51 Hazard: ATMOSPHERE (STAGNANT WATER)
YES
3785ATHLETIC FIELDS AND COURTSVAULTELECNELECTRICAL VAULTNW CORNER OF FIELD UNABLE TO OPEN HATCH.
3785ATHLETIC FIELDS AND COURTSVAULTELECSELECTRICAL VAULTSW CORNER OF SPORT FIELD #2 TOO SMALL TO ENTER. APPROXIMATELY 1 1/2' X 2' AND 3' DEEP.
4055BASEBALL GRANDSTANDEWALLARDEAST OF WALLA WALLA RDHazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1326BOTANY GREENHOUSEVAULTELECELECTRICAL VAULTBY STEVENS WAY Hazard: ATMOSPHERE (TOXIC)
Hazard: ELECTRICAL
SIGN IS IN SPACE, BUT IT IS DOWN.
YES
1187CANOE HOUSEVAULTELECNELECTRICAL VAULTS (2)NORTH OF CANOE HOUSE IN GRASS Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1187CANOE HOUSEVAULTELECWELECTRICAL VAULTOUTSIDE CANOE HOUSE ON WEST SIDE Hazard: OXYGEN DEFICIENCY
YES
1279CHEMISTRY LIBRARY BUILDINGMANHOLETNKMANHOLE ACCESS TO SALTWATER TANK VALVESGRASSY KNOLL SW SIDE OF BUILDING Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (IF PIPE BREAKS - RUSTY AND OLD)
Hazard: ENTRAPMENT
Hazard: FALL HAZARD (18')
YES
1008ELECTRICAL ENGINEERING BUILDINGLIFTSTAT56LIFT STATIONPIT RMB056 Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS), ELECTRICAL
YES
1008ELECTRICAL ENGINEERING BUILDINGLIFTSTAT5ALIFT STATIONLOWER BASEMENT ACROSS FROM STAIR #9 Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMP), ELECTRICAL
YES
1008ELECTRICAL ENGINEERING BUILDINGMECHROOMMECHANICAL ROOMACCESS HATCH IN RM 025 MUST CRAWL IN.
NO
1139GOLF DRIVING RANGE BUILDINGELECHNDHOLELECTRICAL HAND HOLESW CORNER OF GOLF DRIVING RANGE CAN'T GET COMPLETELY INSIDE.
4037GOLF DRIVING RANGE SEWER LIFT STATIONLIFTSTATGOLF DRIVING RANGE LIFT STATIONCLARK ROAD Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULMENT (SEWAGE)
Hazard: ENTRAPMENT
Hazard: MECHANICAL/ELECTRICAL
YES
1149GRAVES HALL, 3910 MONTLAKE BLVD NEVAULTELECELECTRICAL VAULTEAST SIDE OF BUILDING Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1198GUGGENHEIM HALLMECHROOMMECH ROOMROOM 416 NO
1204HANSEE HALLVAULTTRANSOLD TRANSFORMER VAULTFACING BUILDING MAIN ENTRANCE, RIGHT CORNER IN BUSHES Hazard: OXYGEN DEFICIENCY
RECOMMEND FILLING VAULT IN W/ DIRT.
THE LID COULD RUST THROUGH CREATING A FALL HAZARD.
YES
1272HARBORVIEW HALL (MEDICINE)BHH22MRMECHANICAL ROOMMECHANICAL ROOM BHH 22 WORK ACTIVITIES CAN TURN SPACE INTO PRCS
NO
1186HARRIS HYDRAULICS LABORATORYCRWLSPCEUNDER FLOOR CRAWLSPACERMS 101,103,106, OUTSIDE S. SIDE OF BLDG Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: MECHANICAL (EQUIPMENT ON TRACK)
Hazard: ELECTRICAL
YES
1186HARRIS HYDRAULICS LABORATORYHYDAHDTANKHYDRAULIC HEAD TANKROOM 101, WAVE TANK ROOM Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1186HARRIS HYDRAULICS LABORATORYHYDRATANKHYDRAULIC TANKHazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1186HARRIS HYDRAULICS LABORATORYWETWELLWET WELL FOR POND/LAKE WATERHazard: OXYGEN DEFICIENCY
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
APPROXIMATELY 12' DEEP
YES
3798HELISTOP PADVAULTELECELECTRICAL VAULTWEST OF E-14 PARKING LOT, IN HELIPAD CAN'T GET COMPLETELY INSIDE.
1324HITCHCOCK HALLCONDWETWELCONDENSATE WET WELLBASMENT MR Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS), THERMAL (HOT WATER)
YES
1324HITCHCOCK HALLFLRDRWETWFLOOR DRAIN WET WELLBASMENT MR Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS)
YES
3950INDOOR PRACTICE FACILITY (DEMPSEY INDOOR CENTER)VAULTCOMMCOMMUNICATIONS VAULTSW CORNER Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1137INTRAMURAL ACTIVITIES BUILDINGVAULTVAULT - PURPOSE UNKNOWNPARKING AREA E-9 NEAR LIFT STATION Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
YES
1137INTRAMURAL ACTIVITIES BUILDINGVAULTCOMMCOMMUNICATIONS VAULTEAST SIDE OF WALLA WALLA RD Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
APPROXIMATELY 4' DEEP.
YES
1137INTRAMURAL ACTIVITIES BUILDINGVAULTELECNELECTRICAL VAULTOUTSIDE, WEST SIDE, NORTH END OF BUILDING Hazard: OXYGEN DEFICIENCY
Hazard: ENTRAPMENT
YES
1137INTRAMURAL ACTIVITIES BUILDINGVAULTELECWELECTRICAL VAULTEAST SIDE OF WALLA WALLA RD Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1137INTRAMURAL ACTIVITIES BUILDINGVAULTSEATTSEATTLE CITY LIGHT VAULTBY IMA TENNIS COURTS Hazard: OXYGEN DEFICIENCY
THIS SPACE NOT ACCESSED BY UW PERSONNEL.
YES
1177LEWIS HALLVAULTELECELECTRICAL VAULTNEAR ANTENNA Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: ELECTRICAL
YES
3923LIFT STATION AT BOAT STREETLIFTSTATBOAT ST LIFT STATION-WET & DRY SIDESSOUTH SIDE OF BOAT STREET Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
3916LIFT STATION AT COLUMBIA ROADLIFTSTAT-DCOLUMBIA WAY LIFT STATION -DRY SIDECOLUMBIA WAY SOUTH OF I COURT BLVD Hazard: FALL HAZARD
YES
3916LIFT STATION AT COLUMBIA ROADLIFTSTAT-WCOLUMBIA WAY LIFT STATION -WET SIDECOLUMBIA WAY SOUTH OF I COURT BLVD Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
3917LIFT STATION AT DOUGLAS RESEARCHLIFTSTATDOUGLASRSRCH CTR LIFT STAT-WET SIDEBY E-16 PARKING LOT Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
NEED TO CHECK OTHER OPENING WITH RODNEY S.
YES
3918LIFT STATION AT GRAVES BUILDINGLIFTSTATGRAVES FIELD LIFT STATIONCLARK RD Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
Hazard: ENTRAPMENT
YES
3919LIFT STATION AT IMA TENNIS CTSLIFTSTATDIMA LIFT STATION - DRY SIDEE-8 PARKING LOT Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENTRAPMENT
Hazard: FALL (25')
PROJECT SCHEDULED TO MOVE PUMPS ABOVE GROUND.
WILL REMOVE FROM LIST AFTER COMPLETION.
YES
3919LIFT STATION AT IMA TENNIS CTSLIFTSTATWIMA LIFT STATION - WET SIDEE-8 PARKING LOT Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
3920LIFT STATION AT SOUTH CAMPUSLIFTSTATDSOCAMPUS CTR LIFT STATION-DRY SIDENORTH OF SAN JUAN RD Hazard: ATMOSPHERE (SEWER GAS) IF FAN NOT ON CONTINUOUSLY
HERMAN WILL DETERMINE IF FAN RUNS CONTINUOUSLY.
YES
3920LIFT STATION AT SOUTH CAMPUSLIFTSTATWSOCAMPUS CTR LIFT STATION-WET SIDENORTH OF SAN JUAN RD Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
3921LIFT STATION AT STADIUMLIFTSTATSTADIUM EAST SIDE LIFT STATIONWEST SIDE OF WOMEN'S SOFTBALL FIELD Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
Hazard: ELECTRICAL
YES
3922LIFT STATION AT WATERFRONT ACTLIFTSTATWATERFRONTACTIVITIES CTR LIFT STATIONE-12 PARKING LOT Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
YES
4395LIFT STATION OUTSIDE MAG H.S.C./JLIFTSTATDLIFT STATION- DRY SIDEOUTSIDE, NE CORNER OF BUILDING Hazard: ATMOSPHERE (SEWER GAS) FAN NOT CONTINUOUS
THE DRY SIDE WILL BE PRCS
UNTIL THE VENTILATION FAN IS CORRECTED TO RUN CONSTANTLY.
YES
4395LIFT STATION OUTSIDE MAG H.S.C./JLIFTSTATWLIFT STATION- WET SIDEOUTSIDE, NE CORNER OF BUILDING Hazard: ATMOSPHERE (SEWER GAS)
Hazard: FALL HAZARD
Hazard: ENGULFMENT (SEWAGE)
YES
1222MAGNUSON HEALTH SCIENCES CENTER AAHALFSPCE1/2 SPACEBASE OF BB-WING WEST STAIR, -2 LEVEL NO
1304MAGNUSON HEALTH SCIENCES CENTER BCONDPUMPCONDENSATE PUMPB020 Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: ELECTRICAL, MECHANICAL
Hazard: THERMAL
YES
1304MAGNUSON HEALTH SCIENCES CENTER BFLRDRWETWFLOOR DRAIN WET WELLSUB BASEMENT B020 Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT (SMALL ACCESS)
Hazard: MECHANICAL
YES
1304MAGNUSON HEALTH SCIENCES CENTER BVACPRODTNKVACUUM PRODUCER COLLECTION TANKSB020 Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT
Hazard: ENTRAPMENT
Hazard: BIOHAZARD
YES
1223MAGNUSON HEALTH SCIENCES CENTER BBFUMEHOODFUME HOOD EXHAUST TANKBY ELEVATOR BB1700 Hazard: ENTRAPMENT
Hazard: CHEMICAL
YES
1223MAGNUSON HEALTH SCIENCES CENTER BBHOTWATTNKHOT WATER TANKSHazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: THERMAL (HOT WATER)
BBX07-04-10,BBX07-04-06,BBX07-04-02,BBX07-04-04
YES
1223MAGNUSON HEALTH SCIENCES CENTER BBREVOSWATNKREVERSE OSMOSIS WATER TANKSWEST END MR BB1700 Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1223MAGNUSON HEALTH SCIENCES CENTER BBVACRSVRVACUUM TANK RESERVOIRBB1700 Hazard: BIOHAZARD
YES
1328MAGNUSON HEALTH SCIENCES CENTER DCONDWETWELCONDENSATE WET WELLRM001 Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (HOT WATER)
Hazard: THERMAL (STEAM/HOT WATER)
APPROXIMATELY 7' - 8' DEEP
YES
1328MAGNUSON HEALTH SCIENCES CENTER DSUMPFLDRFLOOR DRAIN SUMPRM001 Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: THERMAL (HOT WATER/STEAM)
APPROXIMATELY 8' DEEP.
YES
1328MAGNUSON HEALTH SCIENCES CENTER DVACPRODTNKVACUUM PRODUCER COLLECTION TANKSRM001 Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT
Hazard: BIOHAZARD
DECONTAMINATION AND LOCKOUT REQUIRED PRIOR TO WORK.
YES
1328MAGNUSON HEALTH SCIENCES CENTER DVACPUMPVACUUM PUMPSBSX00-04-12, BSX00-04-11 Hazard: MECHANICAL
Hazard: BIOHAZARD
YES
1328MAGNUSON HEALTH SCIENCES CENTER DVACPUMP2VACUUM PUMPSDSX00-04-13, DSX00-04-14,DSX00-04-15 Hazard: MECHANICAL (FAN BLADES)
Hazard: BIOHAZARD
GUARD ON VACUUM NEEDS REPLACEMENT.
YES
1225MAGNUSON HEALTH SCIENCES CENTER ELIFTSTATSEWER LIFT STATIONCARPENTERS STORAGE ROOM -1 LEVEL D-WING Hazard: ATMOSPHERE (SEWER GAS)
Hazard: ENGULFMENT (SEWAGE)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS), ELECTRICAL
YES
1226MAGNUSON HEALTH SCIENCES CENTER FFUMEHOODFUMEHOOD EXHAUST COLLECTORSOUTH PENTHOUSE F600 Hazard: ATMOSPHERE (TOXIC)
Hazard: ENTRAPMENT
Hazard: CHEMICAL
YES
1226MAGNUSON HEALTH SCIENCES CENTER FHALFSPCE1/2 SPACE TUNNELS (EAST & WEST)MR 001, SOUTH BASEMENT Hazard: ATMOSPHERE (SEWER GAS FROM FLOOR DRAIN)
YES
1226MAGNUSON HEALTH SCIENCES CENTER FREVOSWATNKREVERSE OSMOSIS WATER STORAGE TANKSPENTHOUSE MR Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1226MAGNUSON HEALTH SCIENCES CENTER FWETWELLWET WELLHazard: OXYGEN DEFICIENCY
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMP)
YES
1228MAGNUSON HEALTH SCIENCES CENTER HCONDWETWELCONDENSATE WET WELLBY STEAM HEADER Hazard: OXYGEN DEFICIENCY (STEAM)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: THERMAL (STEAM/HOT WATER)
YES
1228MAGNUSON HEALTH SCIENCES CENTER HFLRDRWETWFLOOR DRAIN WET WELLH-WING SOUTH -2 MR Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS)
YES
1228MAGNUSON HEALTH SCIENCES CENTER HLIFTSTATGROUND WATER LIFT STATIONSW CORNER OF MR NEAR FIRE VALVES IN FLOOR Hazard: ATMOSPHERE (TOXIC)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS), ELECTRICAL
YES
1228MAGNUSON HEALTH SCIENCES CENTER HREVOSWATNKREVERSE OSMOSIS WATER STORAGE-2 BASEMENT MR Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1300MAGNUSON HEALTH SCIENCES CENTER II705FAN ACCESSACCESS HATCH TO FAN IBX-990201ACCESS HATCH CERTAIN WORK ACTIVITIES CAN TURN CS INTO PRCS
NO
1174MAGNUSON HEALTH SCIENCES CENTER JCONDCOLPITCONDENSATE COLLECTOR PITNORTH MECH ROOM BEHIND STEAM HEADER Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: THERMAL (HOT WATER)
YES
1174MAGNUSON HEALTH SCIENCES CENTER JFLRDRWETWFLOOR DRAIN RECEIVER/WET WELLBASEMENT MR NORTH Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS)
YES
1174MAGNUSON HEALTH SCIENCES CENTER JHALFSPCE1/2 SPACE ABOVE SUPPLY FAN FME # 56613MR 003, BASEMENT NO
1174MAGNUSON HEALTH SCIENCES CENTER JREVOSWATNKREVERSE OSMOSIS STORAGE TANKSHazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
YES
1175MAGNUSON HEALTH SCIENCES CENTER RRCONDHOTWELCONDENSATE HOT WELLHazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (HOT WATER)
Hazard: ENTRAPMENT
Hazard: THERMAL (HOT WATER)
YES
1175MAGNUSON HEALTH SCIENCES CENTER RRFLRDRRECFLOOR DRAIN RECEIVERHazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL
APPROXIMATELY 6' DEEP.
YES
1175MAGNUSON HEALTH SCIENCES CENTER RRFLRDRWELLFLOOR DRAIN WELL BY HEATING PUMPSRR-WING SOUTH MECH ROOM Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MOLD
APPROXIMATELY 8-10' DEEP.
YES
1175MAGNUSON HEALTH SCIENCES CENTER RRHALFSPCE1/2 SPACE IN BASEMENTMR 001, THROUGH TUNNEL NO HAZARDS PRESENT. MAY BE INTRODUCED BY WORK.
NO
1168MAGNUSON HEALTH SCIENCES CENTER TCONDPUMPCONDENSATE PUMPS050/010 Hazard: ENGULFMENT (WATER)
Hazard: MECHANICAL (PUMPS)
Hazard: THERMAL (HOT PIPES)
YES
1168MAGNUSON HEALTH SCIENCES CENTER TFLRDRWETWFLOOR DRAIN WET WELLS050/010 Hazard: ATMOSPHERE (STAGNANT WATER)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT
Hazard: MECHANICAL (PUMPS)
YES
1138MARINE SCIENCES BUILDINGDOCKCRAWLSPACE UNDER DOCKACCESS HATCH, REQUIRES LADDERHazard: ATMOSPHERE (METHANE)
YES
3830PARKING LOT E-09VAULTCOMMCOMMUNICATIONS VAULTINTERSECTION OF WALLA WALLA & E-9 PARKING LOT Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
Hazard: VEHICULAR TRAFFIC AT ENTRY POINT
YES
3830PARKING LOT E-09VAULTELECELECTRICAL VAULTINTERSECTION OF WALLA WALLA & E-9 PARKING LOT Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
Hazard: VEHICULAR TRAFFIC AT ENTRY POINT
YES
3830PARKING LOT E-09VAULTELECTELECTRICAL VAULTNEAR TENNIS COURTS Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
3831PARKING LOT E-10VAULTELECELECTRICAL VAULTIN PARKING STALL NEAR STADIUM SOUTH PLAZA Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
3832PARKING LOT E-11VAULTWTRMNWATER MAIN VAULTHazard: ENTRAPMENT
YES
1196PAVILION POOLPOOLMRDRAIN PIT IN MECHANICAL ROOMPOOL DRAIN PIT WORK ACTIVITIES CAN CHANGE AREA TO PRCS
NO
1242PHYSICS-ASTRONOMY BARPITPITHazard: ELECTRICAL
THIS IS A PHYSICS DEPARTMENT SPACE.
YES
1242PHYSICS-ASTRONOMY BARPITSPITSRMS B033, B027, B065, B069 THIS IS A PHYSICS DEPARTMENT SPACE.
NO
1350POWER PLANTAIRRCVRSAIR RECEIVERSOUTSIDE BY TOWERS NO HAZARDS IDENTIFIED.
NO
1350POWER PLANTASHBAGASH BAGHOUSE, RECEIVER, VACUUM PUMPFA-TOP Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENTRAPMENT
YES
1350POWER PLANTBLWDWNTANKCONTINUOUS BLOWDOWN TANKBASEMENT SPACE IS TOO SMALL TO ENTER.
1350POWER PLANTBOILERFIREBOILERS 3,4,5,6,7 FIREBOXHazard: OXYGEN DEFICIENCY (COMBUSTION GASES)
Hazard: ATMOSPHERE(COMBUSTIBLE)
MARK WILL POST.
YES
1350POWER PLANTBOILERSTMBOILERS 3,4,5,6,7 STEAM/MUD DRUMSHazard: OXYGEN DEFICIENCY (RUST OR STEAM LEAK)
Hazard: ENGULFMENT (WATER)
Hazard: ENTRAPMENT (SMALL CYLINDER AND INTERNAL COMPONENTS
Hazard: THERMAL (STEAM)
MARK WILL POST.
YES
1350POWER PLANTBOILRBLWDNBOILER BLOWDOWN TANK ROOMAZ EAST Hazard: OXYGEN DEFICIENCY(STEAM)
Hazard: THERMAL (STEAM)
YES
1350POWER PLANTBRNMIXTNKBRINE MIXING TANKBZ WEST, SIDEWALK OUTSIDE Hazard: ENGULFMENT (WATER)
Hazard: CHEMICAL (SODIUM CHLORIDE)
CONCRETE TANK 10' DEEP.
YES
1350POWER PLANTBRNMIXTNKDBRINE MIXING TANK DEALKELIZERAD NORTH Hazard: CHEMICAL(SODIUM HYDROXIDE RESIDUE)
Hazard: ELECTRICAL
Hazard: MECHANICAL(MIXER)
YES
1350POWER PLANTBRNMIXTNKPBRINE MIXING TANK/POLISHERAD NORTH Hazard: OXYGEN DEFICIENCY
NO MIXER PRESENT (NO MECHANICAL HAZARD).
YES
1350POWER PLANTBRNMIXTNKSBRINE MIXING TANK (STORAGE)AB NORTH Hazard: ELECTRICAL
YES
1350POWER PLANTCHLLWTRTNKCHILLED WATER SURGE TANKDA Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
MARK WILL POST.
YES
1350POWER PLANTCOALBINCOAL BINSFA TOP NO HAZARDS PRESENT.
NO
1350POWER PLANTDEALKALIZRDEALKALIZER (WEST AND EAST)BASEMENT NORTH Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: CHEMICAL (CAUSTIC RESIDUE)
YES
1350POWER PLANTFDWTRDEATRFEEDWATER HEATER E/W DEAERATING TANKDA TANK AREA Hazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (WATER)
Hazard: THERMAL (STEAM)
DUE TO INTERNAL COMPONENTS, .
TANK CANNOT BE ENTERED THROUGH THE MANHOLE.
IF INTERNAL COMPONENTS REMOVED, THIS WOULD BECOME A PRCS.
1350POWER PLANTFDWTRHTERFEEDWATER HEATER & DESUPERHEATER TANKHazard: OXYGEN DEFICIENCY
Hazard: ENGULFMENT (WATER)
Hazard: THERMAL (STEAM)
MARK WILL POST.
YES
1350POWER PLANTFDWTRHTRFEEDWATER HEATER E/W WATERSTORAGE TANKDA TANK AREA Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
Hazard: THERMAL (STEAM)
Hazard: CHEMICAL (SODIUM SULFITE)
YES
1350POWER PLANTFOSINTRSPCFUELOIL STORAGE TANK INTERSTITIALSPACEBZ WEST (OUTSIDE) Hazard: ATMOSPHERE(TOXIC)
Hazard: ATMOSPHERE(COMBUSTIBLE)
Hazard: ENGUFLMENT (DIESEL)
Hazard: FALL
INTERSTITIAL SPACE MAY BE ENTERED
WHEN TANK IS FULL. 35' DEEP.MARK WILL POST.
YES
1350POWER PLANTFOSTANKPITFUEL OIL STORAGE TANK PITBZ WEST (OUTSIDE) Hazard: ATMOSPHERE (TOXIC-FUEL VAPOR)
Hazard: ENGULFMENT (DIESEL)
MARK WILL POST.
YES
1350POWER PLANTFOSTANKPMPFUEL OIL STORAGE TANK PUMP ROOMBZ WEST (OUTSIDE)
1350POWER PLANTHOTWELLHOTWELL (EAST & WEST)AF EAST & AC NORTH Hazard: OXYGEN DEFICIENCY (STEAM LEAK)
Hazard: THERMAL (STEAM)
Hazard: ENGULFMENT(HOT WATER)
APPROXIMATELY 10' DEEP CONCRETE TANK.
YES
1350POWER PLANTHPWATERHTRHP FEEDWATER HEATERBASEMENT INTERIOR IS FULL OF TUBES, NO SPACE INSIDE TO ENTER.
1350POWER PLANTINSTAIRRECINSTRUMENT AIR RECEIVERBASEMENT THERE IS NO WAY TO ENTER THIS PIECE OF EQUIPMENT,
SO IT IS NOT A CONFINED SPACE.
1350POWER PLANTMIXTNKCHLLMIXING TANK, CHILLED WATER TREATMENTMACHINE SHOP Hazard: MECHANICAL (PROPELLER)
Hazard: CHEMICAL (SODIUM NITRITE)
MARK WILL POST.
YES
1350POWER PLANTPOLISHERPOLISHER (WEST, CENTER, AND EAST)BASEMENT NORTH Hazard: OXYGEN DEFICIENCY
Hazard: ENGULFMENT (WATER)
Hazard: THERMAL(HOT WATER)
YES
1350POWER PLANTVAULTELECELECTRICAL VAULTEAST SIDE OF POWER PLANT, N OF SNOHOMISH LANE Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
APPROXIMATELY 8' DEEP.
YES
1350POWER PLANTWATERSOFTRWATER SOFTNER (NORTH & SOUTH)UNDER SOUTH TOWER Hazard: OXYGEN DEFICIENCY (RUST)
Hazard: ENGULFMENT (WATER)
YES
4056SOCCER FIELDVAULTELECELECTRICAL VAULTNEAR STADIUM TRACK AND CONCESSION STANDS TOO SMALL TO ENTER.
NO
1188STADIUMELECHNDHOLELECTRICAL HAND HOLESTADIUM SOUTH PLAZA
1188STADIUMVAULTCOMMCOMMUNICATION VAULTSTADIUM SOUTH PLAZA Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
APPROXIMATELY 4' DEEP.
YES
1188STADIUMVAULTELECNELECTRICAL VAULTNORTH OF NORTH PLAZA Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1188STADIUMVAULTELECSELECTRICAL VAULTNEAR STADIUM SOUTH PLAZA Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
APPROXIMATELY 4' DEEP.
YES
1188STADIUMVAULTSTRLTCOMMUNICATIONS/STREET LIGHT VAULTSTADIUM SOUTH PLAZA TOO SMALL TO ENTER.
4595UW TOWER BLDG CLLBOILERSELECTRIC BOILERS (2) LOCATED IN THE LOWER LEVEL OF BUILDING CINTERIOR OF BOILERSHazard: ATMOSPHERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (WATER)
Hazard: ELECTRICAL
Hazard: THERMAL (HOT WATER)
YES
4596UW TOWER BLDG SLLSUMPWASTE WATER SUMP LOCATED IN LOWER LEVEL MECH ROOMHazard: ATMOSHPERE (OXYGEN DEFICIENCY)
Hazard: ENGULFMENT (WATER)
Hazard: MECHANICAL (PUMP)
YES
4593UW TOWER BLDG TFL23 CHILLERCHILLER #1INTERIOR OF CHILLERHazard: ATMOSPHERE (REFRIGERANT)
YES
4593UW TOWER BLDG TFL23 SUPPLY FANFLOOR 23 MECH ROOM PERIMETER SUPPLY FAN2 ENTRIES - 1 ABOVE FAN, 1 ADJACENT TO FANHazard: MECHANICAL (FAN)
PRCS UNLESS FAN LOCKED OUT (USE LOTO PROCEDURES)
FAN MUST BE BLOCKED TO ELIMINATE FAN BLADE MOVEMENT
YES
4593UW TOWER BLDG TFL23 WATER TANKDOMESTIC WATER STORAGE TANKDOMESTIC WATER STORAGE TANKHazard: ATMOSPHERE(OXYGEN DEFICIENCY - RUST)
Hazard: ENGULFMENT (WATER)
YES
4593UW TOWER BLDG TFL23ELEVATOR3ELEVATOR #3 MECHANICAL ROOMELEVATOR #3 MECHANICAL ROOMHazard: MECHANICAL
CAN BE TEMP RECLASSED AS CS ONCE LOTO OF MACHINERY IS DONE
YES
4593UW TOWER BLDG TFLOOR 23 MECHACCESS INTO WARM AIR FAN 1ACCESS INTO HVAC DUCTWORKHazard: MECHANICAL (FAN)
PRCS UNLESS FAN IS LOCKED OUT (USE LOTO PROCEDURES)
YES
4593UW TOWER BLDG TLLGRNDWTRRLFACCESS TO GROUND WATER RELIEF SYSTEM LOCATED ON LOWER LEVEL OF BUILDING TACCESS THROUGH FLOOR HATCHHazard: ATMOSPHERIC (OXYGEN DEFIIENCY)
Hazard: FALL
YES
4593UW TOWER BLDG TOUTSIDEPLZAVOID IN CANOPIES OVER THE OUTSIDE ENTRY NORTH AND SOUTH PLAZASACCES HATCHESTO INTERSTITIAL SPACE IN CANOPY OVER PLAZASHazard: FALL (CANOPY CANNOT SUPPORT WEIGHT)
YES
4593UW TOWER BLDG TWEST STAIRWELLACCESS HATCH INTO CHASEMEZZANINE LEVEL (M-4) ACCESS HATCHHazard: EMPLOYEES SHOULD BE AWARE OF TASKS THAT CAN CHANGE TO PRCS
NO
1120WATERFRONT ACTIVITIES CENTERVALVEHOUSEVALVE HOUSENORTH OF CANOE HOUSEHazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES
1315WOMEN'S FASTPITCH SOFTBALL BUILDINGVAULTELECELECTRICAL VAULTEAST SIDE NEAR RESTROOMS Hazard: OXYGEN DEFICIENCY
Hazard: ELECTRICAL
YES