| FACNUM | Building | Location | Location Description | Location Detail | Pictures | Hazards | Comments | Permit Required |
|---|---|---|---|---|---|---|---|---|
| 1131 | AEROSPACE AND ENGINEERING RESEARCH BUILDING | TIPEXPTNK | TIP EXPANSION TANK | BASEMENT | LOW PRESSURE INSIDE,OPENING IT WILL VENTILATE (VACUUM). ELECTRIC SENSING UNIT LESS THAN 50V. | NO | ||
| ALL | ALL | ATTIC (CLIMB OR CRAWL TO ACCESS) | ATTICS YOU CLIMB/CRAWL IN ARE CS. WORK ACTIVITIES CONDUCTED IN A CS COULD CHANGE IT TO PRCS. | NO | ||||
| ALL | ALL | ATTIC (WALK IN TO ACCESS) | IF YOU WALK IN AND REMAIN STANDING THEN THE ATTIC IS NOT A CS OR PRCS. | |||||
| ALL | ALL | CEILING PLENUM | CEILINGPLENUMS ARE CS EXCEPT AREAS YOU CAN WALK IN AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS. WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS. | NO | ||||
| ALL | ALL | COOLING TOWER | Hazard: ENTRAPMENT Hazard: MECHANICAL Hazard: ELECTRICAL Hazard: CHEMICAL | YES | ||||
| ALL | ALL | CRAWLSPACE | CRAWLSPACES ARE CS EXCEPT AREAS YOU CAN WALK IN AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS. WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS. | NO | ||||
| ALL | ALL | ELECTRICAL VAULT | Hazard: OXYGEN DEFICIENCY Hazard: VEHICULAR TRAFFIC AT ENTRY POINT | YES | ||||
| ALL | ALL | HVAC PLENUMS W/ACCESS HATCH | PLENUMS ARE CS EXCEPT AREAS YOU CAN WALK IN AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS. WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO PRCS. | NO | ||||
| ALL | ALL | HVAC PLENUMS W/ACCESS HATCH | Hazard: ENTRAPMENT (SMALL SPACE) Hazard: MECHANICAL (FAN) Hazard: ELECTRICAL (FAN MOTOR) | YES | ||||
| ALL | ALL | HVAC PLENUMS W/DOORS | IF YOU CAN WALK INTO THE PLENUM AND STAND IN THE WORK AREA, IT IS NOT A CS. | |||||
| ALL | ALL | PIPE CHASES ACCESSED BY HATCH | PIPECHASES ARE CS EXCEPT AREAS YOU CAN WALK IN AND REMAIN STANDING.THESE ARE NOT CONSIDERED CS. WORK ACTIVITIES CONDUCTED IN CS COULD CHANGE IT TO A PRCS. | NO | ||||
| ALL | ALL | SANITARY SEWER MANHOLES | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||||
| ALL | ALL | STORM DRAIN MANHOLES | Hazard: ATMOSPHERE (TOXIC) Hazard: ENGULFMENT (WATER) | YES | ||||
| 1351 | ANDERSON HALL | UTILTUNNEL | UTILITY TUNNEL | MECHANICAL ROOM OR VIA HATCH IN RM 22 | Hazard: ATMOSPHERE (SEWER GAS FROM FLOOR DRAINS) | YES | ||
| 1180 | ARCHITECTURE HALL | ATTICAUD | ATTIC OVER AUDITORIUM | ACCESS BY ROOF | Hazard: FALL (AREAS WHERE FLOOR IS CEILING FOR ROOM BELOW) | IF CRAWLING, AREAS W/BOARDS ARE CS, AREAS WHERE FALL HAZARD EXISTS ARE PRCS. NEED WR TO COVERHOLES W/PLY.310B 1/2 DOOR NEEDS HINGEREPAIR. | YES | |
| 1180 | ARCHITECTURE HALL | ATTICSPACE | ATTIC SPACE | HATCH OFF STAIRWAY (OVER STUDENT CAFÉ) | Hazard: FALL (FLOOR IS SUSPENDED CEILING FOR ROOM BELOW) | ACCESS IS BY CRAWLING. | YES | |
| 1180 | ARCHITECTURE HALL | PIPECHASE | PIPE CHASE UNDER FLOOR | OUTSIDE ROOMS 13, 32, & 51 | Hazard: ATMOSPHERE (STAGNANT WATER) | YES | ||
| 3785 | ATHLETIC FIELDS AND COURTS | VAULTELECN | ELECTRICAL VAULT | NW CORNER OF FIELD | UNABLE TO OPEN HATCH. | |||
| 3785 | ATHLETIC FIELDS AND COURTS | VAULTELECS | ELECTRICAL VAULT | SW CORNER OF SPORT FIELD #2 | TOO SMALL TO ENTER. APPROXIMATELY 1 1/2' X 2' AND 3' DEEP. | |||
| 4055 | BASEBALL GRANDSTAND | EWALLARD | EAST OF WALLA WALLA RD | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | |||
| 1326 | BOTANY GREENHOUSE | VAULTELEC | ELECTRICAL VAULT | BY STEVENS WAY | Hazard: ATMOSPHERE (TOXIC) Hazard: ELECTRICAL | SIGN IS IN SPACE, BUT IT IS DOWN. | YES | |
| 1187 | CANOE HOUSE | VAULTELECN | ELECTRICAL VAULTS (2) | NORTH OF CANOE HOUSE IN GRASS | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1187 | CANOE HOUSE | VAULTELECW | ELECTRICAL VAULT | OUTSIDE CANOE HOUSE ON WEST SIDE | Hazard: OXYGEN DEFICIENCY | YES | ||
| 1279 | CHEMISTRY LIBRARY BUILDING | MANHOLETNK | MANHOLE ACCESS TO SALTWATER TANK VALVES | GRASSY KNOLL SW SIDE OF BUILDING | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (IF PIPE BREAKS - RUSTY AND OLD) Hazard: ENTRAPMENT Hazard: FALL HAZARD (18') | YES | ||
| 1008 | ELECTRICAL ENGINEERING BUILDING | LIFTSTAT56 | LIFT STATION | PIT RMB056 | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS), ELECTRICAL | YES | ||
| 1008 | ELECTRICAL ENGINEERING BUILDING | LIFTSTAT5A | LIFT STATION | LOWER BASEMENT ACROSS FROM STAIR #9 | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMP), ELECTRICAL | YES | ||
| 1008 | ELECTRICAL ENGINEERING BUILDING | MECHROOM | MECHANICAL ROOM | ACCESS HATCH IN RM 025 | MUST CRAWL IN. | NO | ||
| 1139 | GOLF DRIVING RANGE BUILDING | ELECHNDHOL | ELECTRICAL HAND HOLE | SW CORNER OF GOLF DRIVING RANGE | CAN'T GET COMPLETELY INSIDE. | |||
| 4037 | GOLF DRIVING RANGE SEWER LIFT STATION | LIFTSTAT | GOLF DRIVING RANGE LIFT STATION | CLARK ROAD | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULMENT (SEWAGE) Hazard: ENTRAPMENT Hazard: MECHANICAL/ELECTRICAL | YES | ||
| 1149 | GRAVES HALL, 3910 MONTLAKE BLVD NE | VAULTELEC | ELECTRICAL VAULT | EAST SIDE OF BUILDING | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1198 | GUGGENHEIM HALL | MECHROOM | MECH ROOM | ROOM 416 | NO | |||
| 1204 | HANSEE HALL | VAULTTRANS | OLD TRANSFORMER VAULT | FACING BUILDING MAIN ENTRANCE, RIGHT CORNER IN BUSHES | Hazard: OXYGEN DEFICIENCY | RECOMMEND FILLING VAULT IN W/ DIRT. THE LID COULD RUST THROUGH CREATING A FALL HAZARD. | YES | |
| 1272 | HARBORVIEW HALL (MEDICINE) | BHH22MR | MECHANICAL ROOM | MECHANICAL ROOM BHH 22 | WORK ACTIVITIES CAN TURN SPACE INTO PRCS | NO | ||
| 1186 | HARRIS HYDRAULICS LABORATORY | CRWLSPCE | UNDER FLOOR CRAWLSPACE | RMS 101,103,106, OUTSIDE S. SIDE OF BLDG | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: MECHANICAL (EQUIPMENT ON TRACK) Hazard: ELECTRICAL | YES | ||
| 1186 | HARRIS HYDRAULICS LABORATORY | HYDAHDTANK | HYDRAULIC HEAD TANK | ROOM 101, WAVE TANK ROOM | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | ||
| 1186 | HARRIS HYDRAULICS LABORATORY | HYDRATANK | HYDRAULIC TANK | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | |||
| 1186 | HARRIS HYDRAULICS LABORATORY | WETWELL | WET WELL FOR POND/LAKE WATER | Hazard: OXYGEN DEFICIENCY Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | APPROXIMATELY 12' DEEP | YES | ||
| 3798 | HELISTOP PAD | VAULTELEC | ELECTRICAL VAULT | WEST OF E-14 PARKING LOT, IN HELIPAD | CAN'T GET COMPLETELY INSIDE. | |||
| 1324 | HITCHCOCK HALL | CONDWETWEL | CONDENSATE WET WELL | BASMENT MR | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS), THERMAL (HOT WATER) | YES | ||
| 1324 | HITCHCOCK HALL | FLRDRWETW | FLOOR DRAIN WET WELL | BASMENT MR | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS) | YES | ||
| 3950 | INDOOR PRACTICE FACILITY (DEMPSEY INDOOR CENTER) | VAULTCOMM | COMMUNICATIONS VAULT | SW CORNER | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1137 | INTRAMURAL ACTIVITIES BUILDING | VAULT | VAULT - PURPOSE UNKNOWN | PARKING AREA E-9 NEAR LIFT STATION | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) | YES | ||
| 1137 | INTRAMURAL ACTIVITIES BUILDING | VAULTCOMM | COMMUNICATIONS VAULT | EAST SIDE OF WALLA WALLA RD | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | APPROXIMATELY 4' DEEP. | YES | |
| 1137 | INTRAMURAL ACTIVITIES BUILDING | VAULTELECN | ELECTRICAL VAULT | OUTSIDE, WEST SIDE, NORTH END OF BUILDING | Hazard: OXYGEN DEFICIENCY Hazard: ENTRAPMENT | YES | ||
| 1137 | INTRAMURAL ACTIVITIES BUILDING | VAULTELECW | ELECTRICAL VAULT | EAST SIDE OF WALLA WALLA RD | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1137 | INTRAMURAL ACTIVITIES BUILDING | VAULTSEATT | SEATTLE CITY LIGHT VAULT | BY IMA TENNIS COURTS | Hazard: OXYGEN DEFICIENCY | THIS SPACE NOT ACCESSED BY UW PERSONNEL. | YES | |
| 1177 | LEWIS HALL | VAULTELEC | ELECTRICAL VAULT | NEAR ANTENNA | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: ELECTRICAL | YES | ||
| 3923 | LIFT STATION AT BOAT STREET | LIFTSTAT | BOAT ST LIFT STATION-WET & DRY SIDES | SOUTH SIDE OF BOAT STREET | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 3916 | LIFT STATION AT COLUMBIA ROAD | LIFTSTAT-D | COLUMBIA WAY LIFT STATION -DRY SIDE | COLUMBIA WAY SOUTH OF I COURT BLVD | Hazard: FALL HAZARD | YES | ||
| 3916 | LIFT STATION AT COLUMBIA ROAD | LIFTSTAT-W | COLUMBIA WAY LIFT STATION -WET SIDE | COLUMBIA WAY SOUTH OF I COURT BLVD | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 3917 | LIFT STATION AT DOUGLAS RESEARCH | LIFTSTAT | DOUGLASRSRCH CTR LIFT STAT-WET SIDE | BY E-16 PARKING LOT | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | NEED TO CHECK OTHER OPENING WITH RODNEY S. | YES | |
| 3918 | LIFT STATION AT GRAVES BUILDING | LIFTSTAT | GRAVES FIELD LIFT STATION | CLARK RD | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) Hazard: ENTRAPMENT | YES | ||
| 3919 | LIFT STATION AT IMA TENNIS CTS | LIFTSTATD | IMA LIFT STATION - DRY SIDE | E-8 PARKING LOT | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENTRAPMENT Hazard: FALL (25') | PROJECT SCHEDULED TO MOVE PUMPS ABOVE GROUND. WILL REMOVE FROM LIST AFTER COMPLETION. | YES | |
| 3919 | LIFT STATION AT IMA TENNIS CTS | LIFTSTATW | IMA LIFT STATION - WET SIDE | E-8 PARKING LOT | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 3920 | LIFT STATION AT SOUTH CAMPUS | LIFTSTATD | SOCAMPUS CTR LIFT STATION-DRY SIDE | NORTH OF SAN JUAN RD | Hazard: ATMOSPHERE (SEWER GAS) IF FAN NOT ON CONTINUOUSLY | HERMAN WILL DETERMINE IF FAN RUNS CONTINUOUSLY. | YES | |
| 3920 | LIFT STATION AT SOUTH CAMPUS | LIFTSTATW | SOCAMPUS CTR LIFT STATION-WET SIDE | NORTH OF SAN JUAN RD | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 3921 | LIFT STATION AT STADIUM | LIFTSTAT | STADIUM EAST SIDE LIFT STATION | WEST SIDE OF WOMEN'S SOFTBALL FIELD | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) Hazard: ELECTRICAL | YES | ||
| 3922 | LIFT STATION AT WATERFRONT ACT | LIFTSTAT | WATERFRONTACTIVITIES CTR LIFT STATION | E-12 PARKING LOT | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 4395 | LIFT STATION OUTSIDE MAG H.S.C./J | LIFTSTATD | LIFT STATION- DRY SIDE | OUTSIDE, NE CORNER OF BUILDING | Hazard: ATMOSPHERE (SEWER GAS) FAN NOT CONTINUOUS | THE DRY SIDE WILL BE PRCS UNTIL THE VENTILATION FAN IS CORRECTED TO RUN CONSTANTLY. | YES | |
| 4395 | LIFT STATION OUTSIDE MAG H.S.C./J | LIFTSTATW | LIFT STATION- WET SIDE | OUTSIDE, NE CORNER OF BUILDING | Hazard: ATMOSPHERE (SEWER GAS) Hazard: FALL HAZARD Hazard: ENGULFMENT (SEWAGE) | YES | ||
| 1222 | MAGNUSON HEALTH SCIENCES CENTER AA | HALFSPCE | 1/2 SPACE | BASE OF BB-WING WEST STAIR, -2 LEVEL | NO | |||
| 1304 | MAGNUSON HEALTH SCIENCES CENTER B | CONDPUMP | CONDENSATE PUMP | B020 | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: ELECTRICAL, MECHANICAL Hazard: THERMAL | YES | ||
| 1304 | MAGNUSON HEALTH SCIENCES CENTER B | FLRDRWETW | FLOOR DRAIN WET WELL | SUB BASEMENT B020 | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT (SMALL ACCESS) Hazard: MECHANICAL | YES | ||
| 1304 | MAGNUSON HEALTH SCIENCES CENTER B | VACPRODTNK | VACUUM PRODUCER COLLECTION TANKS | B020 | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT Hazard: ENTRAPMENT Hazard: BIOHAZARD | YES | ||
| 1223 | MAGNUSON HEALTH SCIENCES CENTER BB | FUMEHOOD | FUME HOOD EXHAUST TANK | BY ELEVATOR BB1700 | Hazard: ENTRAPMENT Hazard: CHEMICAL | YES | ||
| 1223 | MAGNUSON HEALTH SCIENCES CENTER BB | HOTWATTNK | HOT WATER TANKS | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: THERMAL (HOT WATER) | BBX07-04-10,BBX07-04-06,BBX07-04-02,BBX07-04-04 | YES | ||
| 1223 | MAGNUSON HEALTH SCIENCES CENTER BB | REVOSWATNK | REVERSE OSMOSIS WATER TANKS | WEST END MR BB1700 | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | ||
| 1223 | MAGNUSON HEALTH SCIENCES CENTER BB | VACRSVR | VACUUM TANK RESERVOIR | BB1700 | Hazard: BIOHAZARD | YES | ||
| 1328 | MAGNUSON HEALTH SCIENCES CENTER D | CONDWETWEL | CONDENSATE WET WELL | RM001 | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (HOT WATER) Hazard: THERMAL (STEAM/HOT WATER) | APPROXIMATELY 7' - 8' DEEP | YES | |
| 1328 | MAGNUSON HEALTH SCIENCES CENTER D | SUMPFLDR | FLOOR DRAIN SUMP | RM001 | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: THERMAL (HOT WATER/STEAM) | APPROXIMATELY 8' DEEP. | YES | |
| 1328 | MAGNUSON HEALTH SCIENCES CENTER D | VACPRODTNK | VACUUM PRODUCER COLLECTION TANKS | RM001 | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT Hazard: BIOHAZARD | DECONTAMINATION AND LOCKOUT REQUIRED PRIOR TO WORK. | YES | |
| 1328 | MAGNUSON HEALTH SCIENCES CENTER D | VACPUMP | VACUUM PUMPS | BSX00-04-12, BSX00-04-11 | Hazard: MECHANICAL Hazard: BIOHAZARD | YES | ||
| 1328 | MAGNUSON HEALTH SCIENCES CENTER D | VACPUMP2 | VACUUM PUMPS | DSX00-04-13, DSX00-04-14,DSX00-04-15 | Hazard: MECHANICAL (FAN BLADES) Hazard: BIOHAZARD | GUARD ON VACUUM NEEDS REPLACEMENT. | YES | |
| 1225 | MAGNUSON HEALTH SCIENCES CENTER E | LIFTSTAT | SEWER LIFT STATION | CARPENTERS STORAGE ROOM -1 LEVEL D-WING | Hazard: ATMOSPHERE (SEWER GAS) Hazard: ENGULFMENT (SEWAGE) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS), ELECTRICAL | YES | ||
| 1226 | MAGNUSON HEALTH SCIENCES CENTER F | FUMEHOOD | FUMEHOOD EXHAUST COLLECTOR | SOUTH PENTHOUSE F600 | Hazard: ATMOSPHERE (TOXIC) Hazard: ENTRAPMENT Hazard: CHEMICAL | YES | ||
| 1226 | MAGNUSON HEALTH SCIENCES CENTER F | HALFSPCE | 1/2 SPACE TUNNELS (EAST & WEST) | MR 001, SOUTH BASEMENT | Hazard: ATMOSPHERE (SEWER GAS FROM FLOOR DRAIN) | YES | ||
| 1226 | MAGNUSON HEALTH SCIENCES CENTER F | REVOSWATNK | REVERSE OSMOSIS WATER STORAGE TANKS | PENTHOUSE MR | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | ||
| 1226 | MAGNUSON HEALTH SCIENCES CENTER F | WETWELL | WET WELL | Hazard: OXYGEN DEFICIENCY Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMP) | YES | |||
| 1228 | MAGNUSON HEALTH SCIENCES CENTER H | CONDWETWEL | CONDENSATE WET WELL | BY STEAM HEADER | Hazard: OXYGEN DEFICIENCY (STEAM) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: THERMAL (STEAM/HOT WATER) | YES | ||
| 1228 | MAGNUSON HEALTH SCIENCES CENTER H | FLRDRWETW | FLOOR DRAIN WET WELL | H-WING SOUTH -2 MR | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS) | YES | ||
| 1228 | MAGNUSON HEALTH SCIENCES CENTER H | LIFTSTAT | GROUND WATER LIFT STATION | SW CORNER OF MR NEAR FIRE VALVES IN FLOOR | Hazard: ATMOSPHERE (TOXIC) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS), ELECTRICAL | YES | ||
| 1228 | MAGNUSON HEALTH SCIENCES CENTER H | REVOSWATNK | REVERSE OSMOSIS WATER STORAGE | -2 BASEMENT MR | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | ||
| 1300 | MAGNUSON HEALTH SCIENCES CENTER I | I705FAN ACCESS | ACCESS HATCH TO FAN IBX-990201 | ACCESS HATCH | CERTAIN WORK ACTIVITIES CAN TURN CS INTO PRCS | NO | ||
| 1174 | MAGNUSON HEALTH SCIENCES CENTER J | CONDCOLPIT | CONDENSATE COLLECTOR PIT | NORTH MECH ROOM BEHIND STEAM HEADER | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: THERMAL (HOT WATER) | YES | ||
| 1174 | MAGNUSON HEALTH SCIENCES CENTER J | FLRDRWETW | FLOOR DRAIN RECEIVER/WET WELL | BASEMENT MR NORTH | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS) | YES | ||
| 1174 | MAGNUSON HEALTH SCIENCES CENTER J | HALFSPCE | 1/2 SPACE ABOVE SUPPLY FAN FME # 56613 | MR 003, BASEMENT | NO | |||
| 1174 | MAGNUSON HEALTH SCIENCES CENTER J | REVOSWATNK | REVERSE OSMOSIS STORAGE TANKS | Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT | YES | |||
| 1175 | MAGNUSON HEALTH SCIENCES CENTER RR | CONDHOTWEL | CONDENSATE HOT WELL | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (HOT WATER) Hazard: ENTRAPMENT Hazard: THERMAL (HOT WATER) | YES | |||
| 1175 | MAGNUSON HEALTH SCIENCES CENTER RR | FLRDRREC | FLOOR DRAIN RECEIVER | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL | APPROXIMATELY 6' DEEP. | YES | ||
| 1175 | MAGNUSON HEALTH SCIENCES CENTER RR | FLRDRWELL | FLOOR DRAIN WELL BY HEATING PUMPS | RR-WING SOUTH MECH ROOM | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MOLD | APPROXIMATELY 8-10' DEEP. | YES | |
| 1175 | MAGNUSON HEALTH SCIENCES CENTER RR | HALFSPCE | 1/2 SPACE IN BASEMENT | MR 001, THROUGH TUNNEL | NO HAZARDS PRESENT. MAY BE INTRODUCED BY WORK. | NO | ||
| 1168 | MAGNUSON HEALTH SCIENCES CENTER T | CONDPUMP | CONDENSATE PUMPS | 050/010 | Hazard: ENGULFMENT (WATER) Hazard: MECHANICAL (PUMPS) Hazard: THERMAL (HOT PIPES) | YES | ||
| 1168 | MAGNUSON HEALTH SCIENCES CENTER T | FLRDRWETW | FLOOR DRAIN WET WELLS | 050/010 | Hazard: ATMOSPHERE (STAGNANT WATER) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT Hazard: MECHANICAL (PUMPS) | YES | ||
| 1138 | MARINE SCIENCES BUILDING | DOCK | CRAWLSPACE UNDER DOCK | ACCESS HATCH, REQUIRES LADDER | Hazard: ATMOSPHERE (METHANE) | YES | ||
| 3830 | PARKING LOT E-09 | VAULTCOMM | COMMUNICATIONS VAULT | INTERSECTION OF WALLA WALLA & E-9 PARKING LOT | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL Hazard: VEHICULAR TRAFFIC AT ENTRY POINT | YES | ||
| 3830 | PARKING LOT E-09 | VAULTELEC | ELECTRICAL VAULT | INTERSECTION OF WALLA WALLA & E-9 PARKING LOT | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL Hazard: VEHICULAR TRAFFIC AT ENTRY POINT | YES | ||
| 3830 | PARKING LOT E-09 | VAULTELECT | ELECTRICAL VAULT | NEAR TENNIS COURTS | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 3831 | PARKING LOT E-10 | VAULTELEC | ELECTRICAL VAULT | IN PARKING STALL NEAR STADIUM SOUTH PLAZA | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 3832 | PARKING LOT E-11 | VAULTWTRMN | WATER MAIN VAULT | Hazard: ENTRAPMENT | YES | |||
| 1196 | PAVILION POOL | POOLMR | DRAIN PIT IN MECHANICAL ROOM | POOL DRAIN PIT | WORK ACTIVITIES CAN CHANGE AREA TO PRCS | NO | ||
| 1242 | PHYSICS-ASTRONOMY BAR | PIT | PIT | Hazard: ELECTRICAL | THIS IS A PHYSICS DEPARTMENT SPACE. | YES | ||
| 1242 | PHYSICS-ASTRONOMY BAR | PITS | PITS | RMS B033, B027, B065, B069 | THIS IS A PHYSICS DEPARTMENT SPACE. | NO | ||
| 1350 | POWER PLANT | AIRRCVRS | AIR RECEIVERS | OUTSIDE BY TOWERS | NO HAZARDS IDENTIFIED. | NO | ||
| 1350 | POWER PLANT | ASHBAG | ASH BAGHOUSE, RECEIVER, VACUUM PUMP | FA-TOP | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENTRAPMENT | YES | ||
| 1350 | POWER PLANT | BLWDWNTANK | CONTINUOUS BLOWDOWN TANK | BASEMENT | SPACE IS TOO SMALL TO ENTER. | |||
| 1350 | POWER PLANT | BOILERFIRE | BOILERS 3,4,5,6,7 FIREBOX | Hazard: OXYGEN DEFICIENCY (COMBUSTION GASES) Hazard: ATMOSPHERE(COMBUSTIBLE) | MARK WILL POST. | YES | ||
| 1350 | POWER PLANT | BOILERSTM | BOILERS 3,4,5,6,7 STEAM/MUD DRUMS | Hazard: OXYGEN DEFICIENCY (RUST OR STEAM LEAK) Hazard: ENGULFMENT (WATER) Hazard: ENTRAPMENT (SMALL CYLINDER AND INTERNAL COMPONENTS Hazard: THERMAL (STEAM) | MARK WILL POST. | YES | ||
| 1350 | POWER PLANT | BOILRBLWDN | BOILER BLOWDOWN TANK ROOM | AZ EAST | Hazard: OXYGEN DEFICIENCY(STEAM) Hazard: THERMAL (STEAM) | YES | ||
| 1350 | POWER PLANT | BRNMIXTNK | BRINE MIXING TANK | BZ WEST, SIDEWALK OUTSIDE | Hazard: ENGULFMENT (WATER) Hazard: CHEMICAL (SODIUM CHLORIDE) | CONCRETE TANK 10' DEEP. | YES | |
| 1350 | POWER PLANT | BRNMIXTNKD | BRINE MIXING TANK DEALKELIZER | AD NORTH | Hazard: CHEMICAL(SODIUM HYDROXIDE RESIDUE) Hazard: ELECTRICAL Hazard: MECHANICAL(MIXER) | YES | ||
| 1350 | POWER PLANT | BRNMIXTNKP | BRINE MIXING TANK/POLISHER | AD NORTH | Hazard: OXYGEN DEFICIENCY | NO MIXER PRESENT (NO MECHANICAL HAZARD). | YES | |
| 1350 | POWER PLANT | BRNMIXTNKS | BRINE MIXING TANK (STORAGE) | AB NORTH | Hazard: ELECTRICAL | YES | ||
| 1350 | POWER PLANT | CHLLWTRTNK | CHILLED WATER SURGE TANK | DA | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) | MARK WILL POST. | YES | |
| 1350 | POWER PLANT | COALBIN | COAL BINS | FA TOP | NO HAZARDS PRESENT. | NO | ||
| 1350 | POWER PLANT | DEALKALIZR | DEALKALIZER (WEST AND EAST) | BASEMENT NORTH | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: CHEMICAL (CAUSTIC RESIDUE) | YES | ||
| 1350 | POWER PLANT | FDWTRDEATR | FEEDWATER HEATER E/W DEAERATING TANK | DA TANK AREA | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (WATER) Hazard: THERMAL (STEAM) | DUE TO INTERNAL COMPONENTS, . TANK CANNOT BE ENTERED THROUGH THE MANHOLE. IF INTERNAL COMPONENTS REMOVED, THIS WOULD BECOME A PRCS. | ||
| 1350 | POWER PLANT | FDWTRHTER | FEEDWATER HEATER & DESUPERHEATER TANK | Hazard: OXYGEN DEFICIENCY Hazard: ENGULFMENT (WATER) Hazard: THERMAL (STEAM) | MARK WILL POST. | YES | ||
| 1350 | POWER PLANT | FDWTRHTR | FEEDWATER HEATER E/W WATERSTORAGE TANK | DA TANK AREA | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) Hazard: THERMAL (STEAM) Hazard: CHEMICAL (SODIUM SULFITE) | YES | ||
| 1350 | POWER PLANT | FOSINTRSPC | FUELOIL STORAGE TANK INTERSTITIALSPACE | BZ WEST (OUTSIDE) | Hazard: ATMOSPHERE(TOXIC) Hazard: ATMOSPHERE(COMBUSTIBLE) Hazard: ENGUFLMENT (DIESEL) Hazard: FALL | INTERSTITIAL SPACE MAY BE ENTERED WHEN TANK IS FULL. 35' DEEP.MARK WILL POST. | YES | |
| 1350 | POWER PLANT | FOSTANKPIT | FUEL OIL STORAGE TANK PIT | BZ WEST (OUTSIDE) | Hazard: ATMOSPHERE (TOXIC-FUEL VAPOR) Hazard: ENGULFMENT (DIESEL) | MARK WILL POST. | YES | |
| 1350 | POWER PLANT | FOSTANKPMP | FUEL OIL STORAGE TANK PUMP ROOM | BZ WEST (OUTSIDE) | ||||
| 1350 | POWER PLANT | HOTWELL | HOTWELL (EAST & WEST) | AF EAST & AC NORTH | Hazard: OXYGEN DEFICIENCY (STEAM LEAK) Hazard: THERMAL (STEAM) Hazard: ENGULFMENT(HOT WATER) | APPROXIMATELY 10' DEEP CONCRETE TANK. | YES | |
| 1350 | POWER PLANT | HPWATERHTR | HP FEEDWATER HEATER | BASEMENT | INTERIOR IS FULL OF TUBES, NO SPACE INSIDE TO ENTER. | |||
| 1350 | POWER PLANT | INSTAIRREC | INSTRUMENT AIR RECEIVER | BASEMENT | THERE IS NO WAY TO ENTER THIS PIECE OF EQUIPMENT, SO IT IS NOT A CONFINED SPACE. | |||
| 1350 | POWER PLANT | MIXTNKCHLL | MIXING TANK, CHILLED WATER TREATMENT | MACHINE SHOP | Hazard: MECHANICAL (PROPELLER) Hazard: CHEMICAL (SODIUM NITRITE) | MARK WILL POST. | YES | |
| 1350 | POWER PLANT | POLISHER | POLISHER (WEST, CENTER, AND EAST) | BASEMENT NORTH | Hazard: OXYGEN DEFICIENCY Hazard: ENGULFMENT (WATER) Hazard: THERMAL(HOT WATER) | YES | ||
| 1350 | POWER PLANT | VAULTELEC | ELECTRICAL VAULT | EAST SIDE OF POWER PLANT, N OF SNOHOMISH LANE | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | APPROXIMATELY 8' DEEP. | YES | |
| 1350 | POWER PLANT | WATERSOFTR | WATER SOFTNER (NORTH & SOUTH) | UNDER SOUTH TOWER | Hazard: OXYGEN DEFICIENCY (RUST) Hazard: ENGULFMENT (WATER) | YES | ||
| 4056 | SOCCER FIELD | VAULTELEC | ELECTRICAL VAULT | NEAR STADIUM TRACK AND CONCESSION STANDS | TOO SMALL TO ENTER. | NO | ||
| 1188 | STADIUM | ELECHNDHOL | ELECTRICAL HAND HOLE | STADIUM SOUTH PLAZA | ||||
| 1188 | STADIUM | VAULTCOMM | COMMUNICATION VAULT | STADIUM SOUTH PLAZA | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | APPROXIMATELY 4' DEEP. | YES | |
| 1188 | STADIUM | VAULTELECN | ELECTRICAL VAULT | NORTH OF NORTH PLAZA | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1188 | STADIUM | VAULTELECS | ELECTRICAL VAULT | NEAR STADIUM SOUTH PLAZA | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | APPROXIMATELY 4' DEEP. | YES | |
| 1188 | STADIUM | VAULTSTRLT | COMMUNICATIONS/STREET LIGHT VAULT | STADIUM SOUTH PLAZA | TOO SMALL TO ENTER. | |||
| 4595 | UW TOWER BLDG C | LLBOILERS | ELECTRIC BOILERS (2) LOCATED IN THE LOWER LEVEL OF BUILDING C | INTERIOR OF BOILERS | Hazard: ATMOSPHERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (WATER) Hazard: ELECTRICAL Hazard: THERMAL (HOT WATER) | YES | ||
| 4596 | UW TOWER BLDG S | LLSUMP | WASTE WATER SUMP LOCATED IN LOWER LEVEL MECH ROOM | Hazard: ATMOSHPERE (OXYGEN DEFICIENCY) Hazard: ENGULFMENT (WATER) Hazard: MECHANICAL (PUMP) | YES | |||
| 4593 | UW TOWER BLDG T | FL23 CHILLER | CHILLER #1 | INTERIOR OF CHILLER | Hazard: ATMOSPHERE (REFRIGERANT) | YES | ||
| 4593 | UW TOWER BLDG T | FL23 SUPPLY FAN | FLOOR 23 MECH ROOM PERIMETER SUPPLY FAN | 2 ENTRIES - 1 ABOVE FAN, 1 ADJACENT TO FAN | Hazard: MECHANICAL (FAN) | PRCS UNLESS FAN LOCKED OUT (USE LOTO PROCEDURES) FAN MUST BE BLOCKED TO ELIMINATE FAN BLADE MOVEMENT | YES | |
| 4593 | UW TOWER BLDG T | FL23 WATER TANK | DOMESTIC WATER STORAGE TANK | DOMESTIC WATER STORAGE TANK | Hazard: ATMOSPHERE(OXYGEN DEFICIENCY - RUST) Hazard: ENGULFMENT (WATER) | YES | ||
| 4593 | UW TOWER BLDG T | FL23ELEVATOR3 | ELEVATOR #3 MECHANICAL ROOM | ELEVATOR #3 MECHANICAL ROOM | Hazard: MECHANICAL | CAN BE TEMP RECLASSED AS CS ONCE LOTO OF MACHINERY IS DONE | YES | |
| 4593 | UW TOWER BLDG T | FLOOR 23 MECH | ACCESS INTO WARM AIR FAN 1 | ACCESS INTO HVAC DUCTWORK | Hazard: MECHANICAL (FAN) | PRCS UNLESS FAN IS LOCKED OUT (USE LOTO PROCEDURES) | YES | |
| 4593 | UW TOWER BLDG T | LLGRNDWTRRLF | ACCESS TO GROUND WATER RELIEF SYSTEM LOCATED ON LOWER LEVEL OF BUILDING T | ACCESS THROUGH FLOOR HATCH | Hazard: ATMOSPHERIC (OXYGEN DEFIIENCY) Hazard: FALL | YES | ||
| 4593 | UW TOWER BLDG T | OUTSIDEPLZA | VOID IN CANOPIES OVER THE OUTSIDE ENTRY NORTH AND SOUTH PLAZAS | ACCES HATCHESTO INTERSTITIAL SPACE IN CANOPY OVER PLAZAS | Hazard: FALL (CANOPY CANNOT SUPPORT WEIGHT) | YES | ||
| 4593 | UW TOWER BLDG T | WEST STAIRWELL | ACCESS HATCH INTO CHASE | MEZZANINE LEVEL (M-4) ACCESS HATCH | Hazard: EMPLOYEES SHOULD BE AWARE OF TASKS THAT CAN CHANGE TO PRCS | NO | ||
| 1120 | WATERFRONT ACTIVITIES CENTER | VALVEHOUSE | VALVE HOUSE | NORTH OF CANOE HOUSE | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES | ||
| 1315 | WOMEN'S FASTPITCH SOFTBALL BUILDING | VAULTELEC | ELECTRICAL VAULT | EAST SIDE NEAR RESTROOMS | Hazard: OXYGEN DEFICIENCY Hazard: ELECTRICAL | YES |