16750
A09/04/001 16750 Add text as follows:
1.6.4.2 "Shallow" IDF Rooms
...of 5,000 ASF or less. There shall be a minimum of
8-feet wide by 4-feet deep...
A09/04/002 16750 Add text as follows:
1.6.4.a Key Card Access Equipment Room
A minimum 4x8 piece sheet of fire-retardant plywood painted
with 2 coats of matte white fire-retardant paint is required to
mount equipment for a key card access system. A 4x4 foot
space shall be assigned for this purpose.
R09/04/003 16750 Replace text for CCTV as follows:
1.8.1.5 CATV
Wireless
Internal Reradiating Systems
A09/04/004 16750 Add text as follows:
1.11 Special Systems Considerations
1.11.1 Wireless
1.11.1.1 Voice
1.11.1.2 Data
1.11.1.3 Internal ReRadiating Systems
For any campus building designated as a high rise (5+ stories)
a special emergency communications system is required which
ties into the campus-wide system.
1.11.1.4 Assignable Classrooms
All assignable classrooms will be provided with basic wireless
infrastructure regardless whether the service is made active.
1.11.2 CATV
1.11.3 Distance Learning
Any auditorium will include the following infrastructure
requirements for UWTV use:
(1) 2" conduit from podium location(s) to projection booth
(or equipment closet)
(1) 4" conduit to hall cable tray to projection booth (or
equipment closet)
(2) 2" conduits, one from each side wall of auditorium to
projection booth (or equipment closet) (or
equipment closet)
(2) 2" conduits, one from each side wall of auditorium to
projection booth (or equipment closet).
A09/04/005 16751 PART 2 Add text as follows:
2.7.1 The backboards in the Router/MDF/IDF Rooms shall be
fire-retardant ...
A09/04/006 16751 PART 2 Add text as follows:
. . . matte white paint. Leave at minimum one identifying mark
unpainted for inspector to verify backboard rating.
A09/04/007 16751 PART 3 Add text as follows:
3.4.1.2.3 Plywood shall be fire-retardant and ...
surfaces, leaving at minimum one identifying mark unpainted
for inspector to verify backboard rating.
16752
OUTSIDE PLANT:
A09/04/008 16752 PART 2 Add text as follows:
2.1.1.2 [under Required Products add]
Avaya TeraSPEED cable
#760004036 5022 012A WXBK [12 count]
#760004044 5022 024A WXBK [24 count]
R09/04/009 16752 PART 2 Replace text as follows:
2.1.2.2.1 Fiber optic cable distribution shelf
Systimax replaces the word Avaya under Rack AND Wall Mount
R09/04/010 16752 PART 2 Replace text as follows:
2.1.2.2.2 Splice Shelf
Systimax replaces the word Avaya
R09/04/011 16752 PART 2
2.1.2.2.3 Splice Organizer
[delete Avaya #105 339 899 [24 capacity]
Replace text as follows:
Rack Mount
----------
Systimax #700 025 588
Wall Mount
----------
Systimax #105 289 664
R09/04/012 16752 PART 2 Replace text as follows:
2.1.2.2.5 SC coupler panel
RACK MOUNT
----------
Systimax #700 168 966 [8 capacity]
[A&E: limited application to be coordinated with C&C]
Systimax #700 011 398 [6 capacity]
WALL MOUNT
----------
[A&E: limited application to be coordinated with C&C]
Systimax #106 371 800 [6 capacity]
R09/04/013 16752 PART 2 Replace text as follows:
2.1.2.2.6 SC singlemode/multimode couplers
Systimax #700 004 807 SC UPC (Blue)
OFS #107 562 142 SC APC (Green)
R09/04/014 16752 PART 2 Replace text as follows:
2.1.2.2.7 Singlemode SC fiber optic connector
Systimax #700 006 976 [SC UPC]
R09/04/015 16752 PART 2 Replace text as follows:
2.1.2.2.8 Multimode SC fiber optic connector
Systimax #700 007 024
R09/04/016 16752 PART 2 Replace text as follows:
2.1.2.2.9 Flat polish SC fiber pigtails
OFS VS1-SCU-UNC-05F [5' Simplex 8.3/125 micron sm SC UPC]
R09/04/017 16752 PART 2 Replace text as follows:
2.1.2.2.10 Angle polish SC fiber pigtails
Systimax #107 761 702 [5' Simplex 8.3/125 micron sm SC APC]
RISER ROOMS:
Volition singlemode fiber is no longer used in the RISER.
D09/04/018 16752 PART 2 Delete text as follows:
2.2.1.2.2 Vertical Riser
3M Volition singlemode fiber optic cable VOL-B924P1
[24-strand plenum]
D09/04/019 16752 PART 2 Delete text as follows:
2.2.1.2.3 IDF to Station
3M Volition singlemode fiber optic cable VOL-H94P1
[4-strand plenum]
R09/04/020 16752 PART 2 Replace text as follows:
2.2.2.2.2.1 Wall Mount Rack
---------------
DELETE: Chatsworth Products Inc. #1196-1-7-18
[Fixed wall mount equipment rack, 19" width, 38-1/2" height
18" depth, universal hole pattern, black, supports up to
200 pounds.
ADD: Chatsworth Products Inc. #11960-718 [24" height]
R09/04/021 16752 PART 2 Replace text as follows:
2.2.2.2.2.1 Vertical Cable Management
------------------------
Corning #CDF-IBS-7-6 for each one
#DCF-HUB-05 need four
A09/04/022 16752 PART 2 Add text as follows:
2.2.2.2.2.1 [insert after section on vertical cable management]
Horizontal Cable Management
---------------------------
Chatsworth Products Inc. #12183-719
[1-1/2" bend radius for compliant installation of
Category 5e or fiber cable]
A09/04/023 16752 PART 2 Add text as follows:
2.2.2.3.1.6 Brickwall Filters
[for use with HuskyTV-HBO]
Required Product:
PD1 Brickwall Filter #PDI-1626 LP-13
STATIONS:
C09/04/024 16752 PART 2 Change text as follows:
2.3.1 Cable
2.3.1.1 Voice and Data
The twisted-pair cable for station drop bundles shall be
four (4)...
A09/04/025 16752 PART 2 Add text as follows:
2.3.1 Cable
2.3.1.1 Voice and Data
[under CM rated products add]
3M Part # - VOL-C5E350RX
[where X denotes color]
[under CMP rated products add]
3M Part # - VOL-C5E350PX
[where X denotes color]
Krone Part non-plenum rated # - ?
Krone Part plenum rated # - (?)TN5ESP-XXxx
Mohawk has many numbers based on jacket color:
Mohawk Part non-plenum rated# -
M55988, M56XXX, M56882, M56XXX, M57286, M58XXX
Mohawk Part plenum rated # -
M55989, M56746, M56XXX, M57XXX, M57XXX, M58XXX
A09/04/026 16752 PART 2 Add text as follows:
2.3.2.1.1 Waterproof Faceplate Cover
For areas that are hosed down or for other reasons require
protection from wet spray
Recommended Product:
Arlington Dri-Box Adapter with non-metallic cover and base
#DBP2C 17857
R09/04/027 16752 PART 2 Replace text as follows:
2.4.1 Elevator phone units
RamTel RR733-924M
R09/04/028 16752 PART 2 Replace text COMPLETELY as follows:
2.4.4 Emergency Blue Light phone units
Required Product:
Stanchion - Talk-A-Phone Radius Power Mount
with Blue Light [UW Custom Color]
#ETP - MTR
Phone Unit - Talk-A-Phone
#ETP-400V
A09/04/029 16752 PART 2 Add text as follows:
2.6.1 Innerduct
Horizontal Pathway:
ENDOT # IPR 1.00 24 17 07-7500
riser rated orange 1" duct
Riser Pathway:
ENDOT #ICE 1.00 32 21 02-7500
non-riser rated orange 1" duct
A09/04/030 16752 PART 3 Add text as follows;
3.3.5.3 WireMold
3.3.5.3.1 Angled Mounting Adapter - Orient to minimize cable bend
radius at jack connection.
3.3.5.3.2 Jack Orientation - The "key" in the jack shall face the
highest ridge on the angled mounting adapter.
3.3.5.3.3 Jack Configuration - Regardless of the orientation of the
angled mounting adapter, configure the jacks as follows:
V1 D1
V2 D2
For data only situations, V1 and V2 position will have
blanks.
A09/04/031 16752 PART 3 Change text as follows:
3.6.2.1.1 ...fiber termination sockets (multimode) or connectors
(singlemode).
and
When terminating Volition multimode cables,
and
...the MDF shall be terminated on the "receive" fiber in
the IDF. When terminating singlemode cables,
the first 75% of connectors whall be SC UPC and
the last 25% shall be SC APC.
A09/04/031 16752 PART 2 Add following text:
3.7.3.7.1 Elevator Phone
...Documents. Elevator cab design shall allow easy access
to telephone unit removal while standing inside the cab
without removing the back wall of the cab.
R09/04/032 SD-CM-44 Jack Position Configurations Replace one detail:
WireMold 4000 (3000) cover
Replacement diagram shows
only 2 bezels on a mounting adapter
[adapter orientation determined by cable feed location]
the key on the jack pointing to the highest ridge
V1/V2 vertically aligned on the left and
D1/D2 vertically aligned on the right
[Jack alignment is not tied to orientation of adapter.]